Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 22, 2017, 08:43 AM
  • 29 0294_29 0287 _22092017_015731.mp4

Date
09/22/2017
W/O
658119
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00375
PipeID
P24204
Time
1:43 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4887
Sewer Name
29 ORANGE AVENUE SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
01
Purpose
Routine Assessment
Project
WO_658119_TV29040_SEP2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0294
Downstream MH
29 0287
Dir. of Survey
Downstream
Length Surveyed
299.9 ft.
Total Length
299.9 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 29 0294 to 29 0287
MH: 29 0294MH: 29 0287downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 02940 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area18.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"20.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"68 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"105.8 ft. CM - Crack Multiple, from 06 to 01 o'clock, within 8 inches of joint: YES109.3 ft. CM - Crack Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES112.7 ft. CM - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES114.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"196.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"298 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH299.9 ft. AMH - Downstream Manhole, Survey Ends - 29 0287299.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (3)

  • Crack Multiple, from 06 to 01 o'clock, within 8 inches of joint: YES

    105.8 ft. - Crack Multiple, from 06 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

    109.3 ft. - Crack Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

    112.7 ft. - Crack Multiple, from 12 to 05 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0AMH29 0294
298MGOSPALLING THROUGHOUT THE REACH
199.5TFC
68TFC
114.4TFC
109.3CM
104TB
196.8TFC
299.9AMH29 0287
18.3TFC
299.9MGOCONNECTION AT MH 9 O'CLOCK
0MWL
0MWM
112.7CM
20.7TFC
105.8CM
70.4TFC
116.8TFC

Properties (7)

additional_info
SC345947
custom_field_two
4
customer
LACSD
datetime
2017-09-22T01:43:49-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid