Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 29, 2021, 09:10 AM
  • B 0620_B 0619_04292021_022450.mp4

Date
04/29/2021
W/O
885818
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00106
PipeID
P09285
Time
2:10 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8794
Sewer Name
B JOINT OUTFALL B - UNIT 8C
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_885818_TV15228_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
21 in.
Upstream MH
B 0620
Downstream MH
B 0619
Dir. of Survey
Downstream
Length Surveyed
405.4 ft.
Total Length
405.4 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
400
O&M Index
2
O&M Quick
2O00
O&M Rating
160
Overall Index
2
Overall Quick
Overall Rating
560
Pipe schematic from manhole B 0620 to B 0619
MH: B 0620MH: B 0619downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 06202 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start3.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.7 ft. MGO - General Observation - MAG COATING THROUGHOUT3.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start402.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish402.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish402.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish405.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE405.4 ft. AMH - Downstream Manhole, Survey Ends - B 0619

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING THROUGHOUT

    3.7 ft. - General Observation - MAG COATING THROUGHOUT

  • General Observation - COCKROACHES IN MANHOLE

    405.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
402.8SAV
402.8DAGS
402.8SSS
0MGOCOCKROACHES IN MANHOLE
0MWM
405.4MGOCOCKROACHES IN MANHOLE
405.4AMHB 0619
3.7SSS
0MWL
3.7MGOMAG COATING THROUGHOUT
0AMHB 0620
2DAGS
3.7SAV

Properties (7)

additional_info
630069042821202
custom_field_three
SPALLING/VISIBLE AGGREGATE
custom_field_two
3
customer
1
datetime
2021-04-29T02:10:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false