Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2021, 10:21 AM
  • B 0617_B 0616_04282021_033318.mp4

Date
04/28/2021
W/O
885818
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00106
PipeID
P09282
Time
3:21 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8792
Sewer Name
B JOINT OUTFALL B - UNIT 8C
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_885818_TV15228_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
21 in.
Upstream MH
B 0617
Downstream MH
B 0616
Dir. of Survey
Downstream
Length Surveyed
325.2 ft.
Total Length
336 ft.
Structural Index
2
Structural Quick
3K2L
Structural Rating
317
O&M Index
2
O&M Quick
412L
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
449
Pipe schematic from manhole B 0617 to B 0616
MH: B 0617MH: B 0616downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - B 06172 ft. MGO - General Observation - MAG COATING THROUGHOUT2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start323.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish323.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish325 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.2 ft. AMH - Downstream Manhole, Survey Ends - B 0616325.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE325.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - MAG COATING THROUGHOUT

    2 ft. - General Observation - MAG COATING THROUGHOUT

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    16.8 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    325.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
325.2AMHB 0616
0MWL
2MGOMAG COATING THROUGHOUT
0MWM
325.2MGOCOCKROACHES IN MANHOLE
0MGOCOCKROACHES IN MANHOLE
2DAGS
0AMHB 0617
325SSS
323.3DAGS
325.2MGOCONNECTION AT MH 3 O'CLOCK
2.1SSS
323.2SAP
16.8SAP

Properties (7)

additional_info
630069042721203
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-04-28T03:21:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false