Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2021, 09:19 AM
  • 05 1653_05 1652_04022021_022636.mp4

Date
04/02/2021
W/O
886227
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06876
Time
2:19 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8720
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
30
Purpose
Routine Assessment
Project
WO_886227_TV05132_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1652
Downstream MH
05 1653
Dir. of Survey
Upstream
Length Surveyed
141 ft.
Total Length
141 ft.
Structural Index
3
Structural Quick
3E2D
Structural Rating
138
O&M Index
2
O&M Quick
2D00
O&M Rating
54
Overall Index
2
Overall Quick
Overall Rating
192
Pipe schematic from manhole 05 1652 to 05 1653
MH: 05 1652MH: 05 1653upstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN0 ft. AMH - Upstream Manhole, Survey Ends - 05 16530.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish49.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"139 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start139 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start139 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start141 ft. MWM - Water Mark, 35 %of cross sectional area141 ft. AMH - Downstream Manhole, Survey Begins - 05 1652141 ft. MWL - Water Level, 30 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
139SSS
2SSS
2CM
140.9MGOCONN @ MH 3 O'CLOCK/CAPPED
2DAGS
140.9CM
0MWM
141MGOCONN @ MH 9 O'CLOCK/UNKNOWN
0AMH05 1652
139DAGS
91.8TFC
141AMH05 1653
0MWL

Properties (7)

additional_info
630074040121201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-04-02T02:19:55-07:00
documentation
PROPIPE
is_lateral_inspection
false