Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2021, 08:54 AM
  • 05 1651_05 1650_04022021_020824.mp4

Date
04/02/2021
W/O
886227
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06874
Time
1:54 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8720
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
30
Purpose
Routine Assessment
Project
WO_886227_TV05132_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1651
Downstream MH
05 1650
Dir. of Survey
Downstream
Length Surveyed
388 ft.
Total Length
388 ft.
Structural Index
3
Structural Quick
423N
Structural Rating
390
O&M Index
2
O&M Quick
312N
O&M Rating
157
Overall Index
2
Overall Quick
Overall Rating
547
Pipe schematic from manhole 05 1651 to 05 1650
MH: 05 1651MH: 05 1650downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16512 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start22.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"62.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN102.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"142.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"183.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 1" - OPEN222.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN262.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"262.6 ft. RMC - Roots Medium Connection, at 12 o'clock, 10 %, within 8 inches of joint: NO294 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES303.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN338.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"382.2 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES383.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish386 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish388 ft. AMH - Downstream Manhole, Survey Ends - 05 1650388 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED388 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    294 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    382.2 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
0MWL
388AMH05 1650
338.8TFA
303.1TFOPEN
388MGOCONN @ MH 3 O'CLOCK/CAPPED
388MGOCONN @ MH 9 O'CLOCK/CAPPED
262.6TFA
2SSS
0MWM
386DAGS
62.9TFOPEN
142.9TFC
262.6RMC
386SSS
183.1TFOPEN
383.8CM
2CM
382.2FM
294FM
22.9TFA
102.4TFA
2DAGS
0AMH05 1651
222.8TFOPEN

Properties (7)

additional_info
630074040121201
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-04-02T01:54:36-07:00
documentation
PROPIPE
is_lateral_inspection
false