Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2021, 05:30 AM
  • 05 1649_05 1648_04012021_224808.mp4

Date
04/01/2021
W/O
886227
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06872
Time
10:30 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8720
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
30
Purpose
Routine Assessment
Project
WO_886227_TV05132_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1649
Downstream MH
05 1648
Dir. of Survey
Downstream
Length Surveyed
399.5 ft.
Total Length
399.5 ft.
Structural Index
3
Structural Quick
4O3O
Structural Rating
711
O&M Index
2
O&M Quick
2O00
O&M Rating
158
Overall Index
3
Overall Quick
Overall Rating
869
Pipe schematic from manhole 05 1649 to 05 1648
MH: 05 1649MH: 05 1648downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 16490 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN62.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"111 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"150.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN195.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN235.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"275.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"314.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"354.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"397 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish397 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish397 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish399.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish399.5 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED399.5 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN399.5 ft. AMH - Downstream Manhole, Survey Ends - 05 1648

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
0AMH05 1649
195.3TFOPEN
0MWM
0MWL
399.5FM
5.5FM
399.5MGOCONN @ MH 9 O'CLOCK/CAPPED
397DAGS
314.9TFA
150.8TFOPEN
2DAGS
2SSS
354.4TFA
31TFOPEN
399.5MGOCONN @ MH 3 O'CLOCK/UNKNOWN
235.5TFA
275.1TFA
62.7TFA
399.5AMH05 1648
111TFC
397CM
2CM
397SSS

Properties (7)

additional_info
630074040121201
custom_field_three
FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-04-01T22:30:43-07:00
documentation
PROPIPE
is_lateral_inspection
false