Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2021, 07:32 AM
  • 05 1645_05 1644_04022021_004634.mp4

Date
04/02/2021
W/O
886227
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06868
Time
12:32 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8720
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
30
Purpose
Routine Assessment
Project
WO_886227_TV05132_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1645
Downstream MH
05 1644
Dir. of Survey
Downstream
Length Surveyed
312.9 ft.
Total Length
312.9 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
248
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
3
Overall Quick
Overall Rating
372
Pipe schematic from manhole 05 1645 to 05 1644
MH: 05 1645MH: 05 1644downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. AMH - Upstream Manhole, Survey Begins - 05 16450 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/CAPPED0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"44.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN60 ft. MWL - Water Level, 30 %of cross sectional area83.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN124.4 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"160 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN200.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN244.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN284.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"310 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish312.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/UNKNOWN312.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1644312.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED312.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"

    124.4 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"

Observations (21)

DistanceCodeObservation
11.8TFA
310DAGS
200.3TFOPEN
83.7TFOPEN
160TFOPEN
60MWL
2DAGS
312.9MGOCONN @ MH 3 O'CLOCK/UNKNOWN
0MGOCONN @ MH 3 O'CLOCK/CAPPED
124.4TBA
0AMH05 1645
2FM
312.9AMH05 1644
44.1TFOPEN
312.9MGOCONN @ MH 9 O'CLOCK/CAPPED
0MGOCONN @ MH 3 O'CLOCK/CAPPED
312.9FM
0MWL
0MWM
244.8TFOPEN
284.2TFC

Properties (7)

additional_info
630074040121201
custom_field_three
FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-04-02T00:32:28-07:00
documentation
PROPIPE
is_lateral_inspection
false