Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2021, 10:39 AM
  • 05 1658A_05 1658_04022021_034900.mp4

Date
04/02/2021
W/O
886227
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06881
Time
3:39 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8720
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Routine Assessment
Project
WO_886227_TV05132_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
05 1658A
Downstream MH
05 1657A
Dir. of Survey
Downstream
Length Surveyed
274.8 ft.
Total Length
274.8 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
273
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
381
Pipe schematic from manhole 05 1658A to 05 1657A
MH: 05 1658AMH: 05 1657Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 05 1658A2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start64.7 ft. MGO - General Observation - MH 05 1658 DOESN'T EXIST.102.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"203.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"272 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish272 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish274.8 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE274.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK274.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish274.8 ft. MGO - General Observation - D/S MH IS 05 1657A, NOT 05 1658.274.8 ft. AMH - Downstream Manhole, Survey Ends - 05 1657A

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MWL
102.7TFC
64.7MGOMH 05 1658 DOESN'T EXIST.
2DAGS
0MWM
274.8MGOCONN @ MH 3 O'CLOCK/ACTIVE
274.8MGOCONN @ MH 9 O'CLOCK
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
274.8CM
203.6TFC
2SSS
0AMH05 1658A
274.8MGOD/S MH IS 05 1657A, NOT 05 1658.
272DAGS
274.8AMH05 1657A
272SSS
2CM

Properties (7)

additional_info
630074040121201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-04-02T03:39:04-07:00
documentation
PROPIPE
is_lateral_inspection
false