Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2021, 09:39 AM
  • 05 1655_05 1654_04022021_025127.mp4

Date
04/02/2021
W/O
886227
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00539
PipeID
P06878
Time
2:39 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8720
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
30
Purpose
Routine Assessment
Project
WO_886227_TV05132_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
12 in.
Upstream MH
05 1654
Downstream MH
05 1655
Dir. of Survey
Upstream
Length Surveyed
298.4 ft.
Total Length
298.4 ft.
Structural Index
3
Structural Quick
3K22
Structural Rating
178
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
2
Overall Quick
Overall Rating
296
Pipe schematic from manhole 05 1654 to 05 1655
MH: 05 1654MH: 05 1655upstream0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 16550 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish106.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN155.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"199.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"243 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"285.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"296.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start296.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start296.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start298.4 ft. AMH - Downstream Manhole, Survey Begins - 05 1654298.4 ft. MWL - Water Level, 20 %of cross sectional area298.4 ft. MWM - Water Mark, 25 %of cross sectional area

Observations (17)

DistanceCodeObservation
191.7TFOPEN
2DAGS
0AMH05 1654
296SSS
298.4MGOCONN @ MH 9 O'CLOCK/ACTIVE
55.4TFC
0MWL
13.1TFA
2SSS
298.4CM
296DAGS
143.1TFC
0MWM
98.8TFA
298.4AMH05 1655
298.4MGOCONN @ MH 3 O'CLOCK/ACTIVE
2CM

Properties (7)

additional_info
630074040121201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-04-02T02:39:40-07:00
documentation
PROPIPE
is_lateral_inspection
false