Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 22, 2021, 10:01 AM
  • 15 0334_15 0333_04222021_032932.mp4

Date
04/22/2021
W/O
886343
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00598
PipeID
P12260
Time
3:01 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8787
Sewer Name
15 BALDWIN PARK TRUNK
City
BALDWIN PARK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_886343_TV15016_APR2021
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
15 0333
Downstream MH
15 0334
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 15 0333 to 15 0334
MH: 15 0333MH: 15 0334upstream0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF UPLEG OF D/S EAST SIPHON.0 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES0 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES2 ft. AMH - Downstream Manhole, Survey Begins - 15 0333 EAST SIPHON2 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (3)

  • Survey Abandoned - VIEW OF UPLEG OF D/S EAST SIPHON.

    2 ft. - Survey Abandoned - VIEW OF UPLEG OF D/S EAST SIPHON.

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
0AMH15 0333 EAST SIPHON
0MWM
2DAGS
2MSAVIEW OF UPLEG OF D/S EAST SIPHON.
0MWL
2SRV
2SAP

Properties (7)

additional_info
630069042121203
custom_field_three
PROJECTING AGGREGATE/VISIBLE REINFORCEMENT
custom_field_two
2
customer
1
datetime
2021-04-22T03:01:13-07:00
documentation
PRO PIPE
is_lateral_inspection
false