Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2021, 10:45 AM
  • J 0233_J 0232_552021_034955.mp4

Date
05/05/2021
W/O
0879983
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11479
Time
3:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1797
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47
Purpose
Capital Improvement Program Assesment
Project
20210505MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0233
Downstream MH
J 0232
Dir. of Survey
Downstream
Length Surveyed
220.7 ft.
Total Length
220.7 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
16
Pipe schematic from manhole J 0233 to J 0232
MH: J 0233MH: J 0232downstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0 ft. AMH - Upstream Manhole, Survey Begins - 3:50AM2 ft. MGO - General Observation - 60% OLD MAG COAT START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE6.9 ft. SSS - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE33.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC183 ft. SAM - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEV ERE AGG186.2 ft. SAM - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG201.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR220.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE220.4 ft. MGO - General Observation - 60% OLD MAG COAT FINISH220.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG SPORATIC220.7 ft. MSA - Survey Abandoned - OUT OF CCTV CABLE WILL COMPLETE REVERSE INSPECTION( 4:15AM)

Observation photos (6)

  • General Observation - 60% OLD MAG COAT START

    2 ft. - General Observation - 60% OLD MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    6.9 ft. - Surface Spalling, from 08 to 12 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

    33.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG SPORATIC

  • Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEV ERE AGG

    183 ft. - Surface Aggregate Missing, from 08 to 09 o'clock, within 8 inches of joint: YES, Start - SEV ERE AGG

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    201.7 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

Observations (14)

DistanceCodeObservation
0MGOConn. @ Mh, 9 O' Clock. OPEN
2MGO60% OLD MAG COAT START
33.7SAVSEVERE AGG SPORATIC
220.7MSAOUT OF CCTV CABLE WILL COMPLETE REVERSE INSPECTION( 4:15AM)
220.4SSSBLISTERING PEELING CONCRETE
201.7SRCCIRCUM REBAR
220.4MGO60% OLD MAG COAT FINISH
0MGOConn. @ Mh, 3 O' Clock. Capped
183SAMSEV ERE AGG
6.9SSSPEELING CONCRETE
2SSSBLISTERING PEELING CONCRETE
0AMH3:50AM
220.4SAVSEVERE AGG SPORATIC
186.2SAMSEVERE AGG

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2021-05-05T03:45:05-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false