Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2021, 09:05 AM
  • J 0235A_J 0235_552021_021848.mp4

Date
05/05/2021
W/O
0879983
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P11482
Time
2:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1797
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47
Purpose
Capital Improvement Program Assesment
Project
20210505MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0235A
Downstream MH
J 0235
Dir. of Survey
Downstream
Length Surveyed
82.6 ft.
Total Length
82.6 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole J 0235A to J 0235
MH: J 0235AMH: J 0235downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. MGO - General Observation - 80% OLD MAG COAT START2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE28.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE81.9 ft. MGO - General Observation - MAG COAT 80% FINISH81.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE82.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active82.6 ft. AMH - Downstream Manhole, Survey Ends - 2:20AM

Observation photos (3)

  • General Observation - 80% OLD MAG COAT START

    2 ft. - General Observation - 80% OLD MAG COAT START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    28.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

Observations (11)

DistanceCodeObservation
28.5SSSBLISTERING CONCRETE
0MWL
0MWM
2MGO80% OLD MAG COAT START
0AMH2:10AM
82.2MGOConn. @ Mh, 3 O' Clock. Active
2SSSBLISTERING PEELING CONCRETE
81.9MGOMAG COAT 80% FINISH
81.9SSSBLISTERING PEELING CONCRETE
82.6AMH2:20AM
0MGOConn. @ Mh, 3 O' Clock. Active

Properties (6)

custom_field_three
BLISTERING PEELING CONCRETE
custom_field_two
3
customer
LACSD
datetime
2021-05-05T02:05:00-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false