Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2021, 08:02 AM
  • J 0236_J 0235A_552021_013829.mp4

Date
05/05/2021
W/O
0879983
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00057
PipeID
P22998
Time
1:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1797
Sewer Name
J JOINT OUTFALL J - UNIT 1E
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47
Purpose
Capital Improvement Program Assesment
Project
20210505MDM_JOINT_OUTFALL_J_UNIT_1E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
J 0236
Downstream MH
J 0235A
Dir. of Survey
Downstream
Length Surveyed
323.4 ft.
Total Length
323.4 ft.
Structural Index
3
Structural Quick
5123
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole J 0236 to J 0235A
MH: J 0236MH: J 0235Adownstream0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Capped0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:15AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 70% START4 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - long rebar78.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE196.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETEW323.4 ft. AMH - Downstream Manhole, Survey Ends - 1:45AM323.4 ft. MGO - General Observation - 70% MAG COAT FINISH323.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 70% START

    2 ft. - General Observation - MAG COAT 70% START

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - long rebar

    4 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - long rebar

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    78.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETEW

    196.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETEW

Observations (12)

DistanceCodeObservation
2SSSBLISTERING PEELING CONCRETE
0MGOConn. @ Mh, 9 O' Clock. Capped
78.2SSSBLISTERING CONCRETE
4SRClong rebar
196.7SSSPEELING CONCRETEW
323.4AMH1:45AM
323.4MGO70% MAG COAT FINISH
0MWL
323.4SSSBLISTERING PEELING CONCRETE
2MGOMAG COAT 70% START
0MWM
0AMH1:15AM

Properties (6)

custom_field_three
1 LONG REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2021-05-05T01:02:59-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false