Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2021, 04:43 AM
  • 02 0648_02 0647_03242021_220408.mp4

Date
03/24/2021
W/O
886194
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00258
PipeID
P03202
Time
9:43 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8668
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_886194_TV02384_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 0648
Downstream MH
02 0647
Dir. of Survey
Downstream
Length Surveyed
291.9 ft.
Total Length
291.9 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
295
O&M Index
2
O&M Quick
2K00
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
419
Pipe schematic from manhole 02 0648 to 02 0647
MH: 02 0648MH: 02 0647downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 06480 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start11.4 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"18.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES35.6 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.2 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES85.3 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"121.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"126 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"191 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"203 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"215 ft. MWM - Water Mark, 30 %of cross sectional area236.1 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"284.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN289 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish291.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish291.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0647

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    18.3 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    83.2 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
0AMH02 0648
18.3CM
0MWL
2SSS
291.1DAGS
0MWM
121.7TBA
126TBC
83.2FM
35.6TBC
284.4TBOPEN
11.4TBC
291.1CM
291.9AMH02 0647
93.5TBA
289SSS
215MWM
203TBA
85.3TBA
236.1TBC
2CM
191TBA
2DAGS

Properties (7)

additional_info
630138032421201
custom_field_three
CONTINUOUS CRACKS
custom_field_two
3
customer
1
datetime
2021-03-24T21:43:56-07:00
documentation
PROPIPE
is_lateral_inspection
false