Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2021, 05:27 AM
  • 02 0692_02 0645_03242021_224257.mp4

Date
03/24/2021
W/O
886194
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00258
PipeID
P03199
Time
10:27 PM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8668
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_886194_TV02384_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 0692
Downstream MH
02 0645
Dir. of Survey
Downstream
Length Surveyed
182.4 ft.
Total Length
182.4 ft.
Structural Index
2
Structural Quick
322F
Structural Rating
78
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
2
Overall Quick
Overall Rating
154
Pipe schematic from manhole 02 0692 to 02 0645
MH: 02 0692MH: 02 0645downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 06920 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"18 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"180 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish180 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish180 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish182.3 ft. MGO - General Observation - ROACHES @ MH182.4 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ABANDONED182.4 ft. AMH - Downstream Manhole, Survey Ends - 02 0645

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
2DAGS
0MWL
13.9TBC
182.4MGOCONN @ MH 3 O'CLOCK/ABANDONED
180DAGS
180SSS
0MWM
180CM
182.4AMH02 0645
2CM
182.3MGOROACHES @ MH
0AMH02 0692
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2SSS
18TBC

Properties (7)

additional_info
630138032421201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-03-24T22:27:47-07:00
documentation
PROPIPE
is_lateral_inspection
false