Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2021, 10:33 AM
  • 02 0625_02 2181_03252021_035444.mp4

Date
03/25/2021
W/O
886194
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00258
PipeID
P03175
Time
3:33 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8668
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
RFIR_WO_886194_TV02384_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 0625
Downstream MH
02 2181
Dir. of Survey
Downstream
Length Surveyed
314.8 ft.
Total Length
314.8 ft.
Structural Index
3
Structural Quick
433L
Structural Rating
334
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
466
Pipe schematic from manhole 02 0625 to 02 2181
MH: 02 0625MH: 02 2181downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 06250 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"209 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"258 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"312 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish312 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish312 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish314.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES314.8 ft. AMH - Downstream Manhole, Survey Ends - 02 2181

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    314.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
314.8AMH02 2181
40.9TBA
312DAGS
312SSS
2SSS
148.2TBA
314.2FM
0AMH02 0625
258TBC
2DAGS
0MWM
299.4TBC
95.1TBC
0MWL
209TBC
2CM
312CM

Properties (6)

additional_info
630138032421201
custom_field_two
3
customer
1
datetime
2021-03-25T03:33:35-07:00
documentation
PROPIPE
is_lateral_inspection
false