Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 8, 2015, 09:43 AM
  • D 0187 D 0186 12082015 Manual.mp4

Date
12/08/2015
W/O
0531069
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00159
PipeID
P10084
Time
1:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6662
Sewer Name
D JOINT OUTFALL D - UNIT 8
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20151204MDM_JOINT_OUTFALL_D_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
54 in.
Upstream MH
D 0187
Downstream MH
D 0186
Dir. of Survey
Downstream
Length Surveyed
680.7 ft.
Total Length
680.7 ft.
Structural Index
5
Structural Quick
5`4Z
Structural Rating
1364
O&M Index
4
O&M Quick
514T
O&M Rating
429
Overall Index
4
Overall Quick
Overall Rating
1793
Pipe schematic from manhole D 0187 to D 0186
MH: D 0187MH: D 0186downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MGO - General Observation - MH CONN ACTIVE 9:000 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED % MISSING2 ft. MGO - General Observation - MISSING TILES 100% 9:00 TO 3:00 START2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR CORRODED & MISSING16 ft. DSZ - Deposits Settled Other, 30 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO - FALLEN TILES SLUDGE16 ft. DSZ - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE20.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR CORRODED & MISSING25.3 ft. MGO - General Observation - MISSING TILES 30%60.1 ft. MGO - General Observation - MISSING TILES 20%73.2 ft. MGO - General Observation - MISSING TILES 20%86 ft. DSZ - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE91.5 ft. MGO - General Observation - MISSING TILES 10%98.9 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish98.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish98.9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR111.1 ft. SRV - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM113.1 ft. MGO - General Observation - MISSING TILES 30%127.8 ft. SRC - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG175.2 ft. DSZ - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start - FALLEN TILES SLUDGE175.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM & LONG199.3 ft. MGO - General Observation - MISSING TILES 30%230.1 ft. DSZ - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE247 ft. MGO - General Observation - MISSING TILES 40%284.9 ft. MGO - General Observation - MISSING TILES 20%299.5 ft. DSZ - Deposits Settled Other, 35 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE324.6 ft. MGO - General Observation - MISSING TILES 20%333.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES387.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES464.6 ft. MGO - General Observation - MISSING TILES 70%543.7 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES648.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES652.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM672.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED & MISSING680.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM & LONG680.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG680.2 ft. DSZ - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Finish - FALLEN TILES SLUDGE680.7 ft. AMH - Downstream Manhole, Survey Ends - 5:05AM

Observation photos (29)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED % MISSING

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR CORRODED % MISSING

  • General Observation - MISSING TILES 100% 9:00 TO 3:00 START

    2 ft. - General Observation - MISSING TILES 100% 9:00 TO 3:00 START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR CORRODED & MISSING

  • Deposits Settled Other,  30 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO - FALLEN TILES SLUDGE

    16 ft. - Deposits Settled Other, 30 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO - FALLEN TILES SLUDGE

  • Deposits Settled Other,  30 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - FALLEN TILES SLUDGE

    16 ft. - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR CORRODED & MISSING

    20.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - LONG & CIRCUM REBAR CORRODED & MISSING

  • General Observation - MISSING TILES 30%

    25.3 ft. - General Observation - MISSING TILES 30%

  • General Observation - MISSING TILES 20%

    60.1 ft. - General Observation - MISSING TILES 20%

  • General Observation - MISSING TILES 20%

    73.2 ft. - General Observation - MISSING TILES 20%

  • Deposits Settled Other,  30 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - FALLEN TILES SLUDGE

    86 ft. - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE

  • General Observation - MISSING TILES 10%

    91.5 ft. - General Observation - MISSING TILES 10%

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

    98.9 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

  • Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM

    111.1 ft. - Surface Reinforcement Visible, from 09 to 10 o'clock, within 8 inches of joint: NO - CIRCUM

  • General Observation - MISSING TILES 30%

    113.1 ft. - General Observation - MISSING TILES 30%

  • Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

    127.8 ft. - Surface Reinforcement Corroded, from 12 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

  • Deposits Settled Other,  30 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: NO, Start - FALLEN TILES SLUDGE

    175.2 ft. - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start - FALLEN TILES SLUDGE

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM & LONG

    175.2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM & LONG

  • General Observation - MISSING TILES 30%

    199.3 ft. - General Observation - MISSING TILES 30%

  • Deposits Settled Other,  30 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - FALLEN TILES SLUDGE

    230.1 ft. - Deposits Settled Other, 30 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE

  • General Observation - MISSING TILES 40%

    247 ft. - General Observation - MISSING TILES 40%

  • General Observation - MISSING TILES 20%

    284.9 ft. - General Observation - MISSING TILES 20%

  • Deposits Settled Other,  35 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES - FALLEN TILES SLUDGE

    299.5 ft. - Deposits Settled Other, 35 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES - FALLEN TILES SLUDGE

  • General Observation - MISSING TILES 20%

    324.6 ft. - General Observation - MISSING TILES 20%

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

    333.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

    387.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    543.7 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

    648.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

    652.8 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED & MISSING

    672.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CORRODED & MISSING

Observations (41)

DistanceCodeObservation
230.1DSZFALLEN TILES SLUDGE
175.2DSZFALLEN TILES SLUDGE
16DSZFALLEN TILES SLUDGE
2SRCCIRCUM REBAR CORRODED % MISSING
2MGOMISSING TILES 100% 9:00 TO 3:00 START
20.4SRCLONG & CIRCUM REBAR CORRODED & MISSING
98.9SRC
98.9SRC
247MGOMISSING TILES 40%
0AMH4:10AM
652.8SRCCIRCUM
0MGOMH CONN ACTIVE 9:00
543.7SRV
680.2SRVCIRCUM & LONG
2SAMSEVERE AGG
648.6SRC
91.5MGOMISSING TILES 10%
2SRCLONG REBAR CORRODED & MISSING
299.5DSZFALLEN TILES SLUDGE
284.9MGOMISSING TILES 20%
98.9SRVCIRCUM & LONG REBAR
199.3MGOMISSING TILES 30%
680.7AMH5:05AM
387.5SRC
127.8SRCCIRCUM & LONG
0MWL
464.6MGOMISSING TILES 70%
680.2SAMSEVERE AGG
0MWM
113.1MGOMISSING TILES 30%
175.2SRVCIRCUM & LONG
680.2DSZFALLEN TILES SLUDGE
16DSZFALLEN TILES SLUDGE
111.1SRVCIRCUM
324.6MGOMISSING TILES 20%
672.3SRCCORRODED & MISSING
60.1MGOMISSING TILES 20%
25.3MGOMISSING TILES 30%
333.2SRC
86DSZFALLEN TILES SLUDGE
73.2MGOMISSING TILES 20%

Properties (6)

custom_field_three
CORRODED MISSING REBAR SPORATIC
custom_field_two
1
customer
LACSD
datetime
2015-12-08T01:43:18-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false