- Date
- 12/08/2015
- W/O
- 0531069
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00159
- PipeID
- P21971
- Time
- 12:23 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6661
- Sewer Name
- D JOINT OUTFALL D - UNIT 8
- City
- TORRANCE
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 08
- Page No.
- 13
- Purpose
- Capital Improvement Program Assesment
- Project
- 20151204MDM_JOINT_OUTFALL_D_UNIT_8
- Material
- RCP-CTL
- Shape
- Circular
- Height
- 54 in.
- Upstream MH
- D 0188
- Downstream MH
- A 0955
- Dir. of Survey
- Downstream
- Length Surveyed
- 75.4 ft.
- Total Length
- 75.4 ft.
- Structural Index
- 3
- Structural Quick
- 3B00
- Structural Rating
- 45
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 49
Pipe schematic from manhole D 0188 to A 0955 Observation photos (7)

2 ft. - General Observation - TILES 100% IN PLACE 9:00 TO 3:00 START

27.5 ft. - General Observation - MISSING TILES 30%

27.5 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

35.4 ft. - General Observation - MISSING TILES 30%

35.4 ft. - General Photograph

44.2 ft. - General Observation - MISSING TILES 5% START

62.1 ft. - General Observation - MISSING TILES 100% START