Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 12:05 PM
  • D 0139_D 0138_12042015_Manual.mp4

Date
12/04/2015
W/O
0531069
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00159
PipeID
P10077
Time
4:05 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6659
Sewer Name
D JOINT OUTFALL D - UNIT 8
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151204MDM_JOINT_OUTFALL_D_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
54 in.
Upstream MH
D 0139
Downstream MH
D 0138
Dir. of Survey
Downstream
Length Surveyed
657.5 ft.
Total Length
657.5 ft.
Structural Index
5
Structural Quick
5v4Y
Structural Rating
1889
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
1893
Pipe schematic from manhole D 0139 to D 0138
MH: D 0139MH: D 0138downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. MGO - General Observation - MISSING TILES 100%9:00 TO 3:00 START2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE5.6 ft. SRV - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: NO - LONG5.6 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG7.3 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - BROKEN54.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: YES - CIRCUM & LONG62.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO88.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR88.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish205.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM LONG REBAR323.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG496.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM589 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING592.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish651.1 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM & LONG657 ft. MGO - General Observation - MISSING TILES 100% FINISH657 ft. MGO - General Observation - MH CONN ACTIVE 3:00657 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM & LONG REBAR657 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish657 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM &LONG REBAR657.5 ft. AMH - Downstream Manhole, Survey Ends - 4:55AM

Observation photos (14)

  • General Observation - MISSING TILES 100%9:00 TO 3:00 START

    2 ft. - General Observation - MISSING TILES 100%9:00 TO 3:00 START

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG

  • Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: NO - LONG

    5.6 ft. - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: NO - LONG

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG

    5.6 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - BROKEN

    7.3 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: YES - BROKEN

  • Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

    54.3 ft. - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

    62.9 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

    88.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM & LONG REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM LONG REBAR

    205.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM LONG REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

    323.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

    496.9 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - CIRCUM

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING

    589 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM & LONG

    651.1 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM & LONG

Observations (26)

DistanceCodeObservation
657MGOMISSING TILES 100% FINISH
2MGOMISSING TILES 100%9:00 TO 3:00 START
657MGOMH CONN ACTIVE 3:00
2SRVCIRCUM
2SRCCIRCUM & LONG
62.9SRC
0MWM
0AMH4:15AM
0MWL
657.5AMH4:55AM
2SAMSEVERE
651.1SRCCIRCUM & LONG
657SRCCIRCUM & LONG REBAR
54.3SRCCIRCUM & LONG
592.7SRC
88.7SRCCIRCUM & LONG REBAR
7.3SRCBROKEN
323.6SRCCIRCUM & LONG
657SAM
657SRCCIRCUM &LONG REBAR
205.1SRCCIRCUM LONG REBAR
5.6SRVLONG
496.9SRCCIRCUM
88.7SRV
5.6SRCLONG
589SRCBROKEN MISSING

Properties (6)

custom_field_three
CORRODED-BROKEN REBAR
custom_field_two
1
customer
LACSD
datetime
2015-12-04T04:05:29-08:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false