Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 4, 2015, 08:38 AM
  • D 0140_D 0139_12042015_Manual.mp4

Date
12/04/2015
W/O
0531069
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00159
PipeID
P10078
Time
12:38 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6659
Sewer Name
D JOINT OUTFALL D - UNIT 8
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Capital Improvement Program Assesment
Project
20151204MDM_JOINT_OUTFALL_D_UNIT_8
Material
RCP-CTL
Shape
Circular
Height
54 in.
Upstream MH
D 0140
Downstream MH
D 0139
Dir. of Survey
Downstream
Length Surveyed
662.6 ft.
Total Length
662.6 ft.
Structural Index
5
Structural Quick
5“4Y
Structural Rating
2628
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
2632
Pipe schematic from manhole D 0140 to D 0139
MH: D 0140MH: D 0139downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:40AM0 ft. MWL - Water Level, 45 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. MGO - General Observation - MH CONN ACTIVE 9:000 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE2 ft. MGO - General Observation - MISSING TILES 100% 9:00 TO 3:00 START2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM3 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM8.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR10.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR10.5 ft. SRV - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES - LONG49.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUN & LONG49.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CORRODED BEYOUND REBAR63.8 ft. MGO - General Observation - 3 REMAINING TILES129.1 ft. MGO - General Observation - MISSING TILES 80%203.7 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG203.7 ft. SRC - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Finish205.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish205.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM221.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG226.2 ft. SRV - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: YES - LONG253.4 ft. SRV - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES - LONG399.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM405 ft. SRV - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES - LONG441 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUN LONG459.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM464.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCU & LONG529 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM556 ft. SRV - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: NO - LONG569 ft. SRC - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM LONG580.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO, Finish585.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES631.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM LONG CORRODED & BROKEN633 ft. MGP - General Photograph - BROKEN REBAR655.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR662.2 ft. MGO - General Observation - MISSING TILES 100% FINISH662.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE662.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM662.2 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG662.2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CIRCUM LONG REBAR662.6 ft. AMH - Downstream Manhole, Survey Ends - 3:50AM

Observation photos (27)

  • General Observation - MISSING TILES 100% 9:00 TO 3:00 START

    2 ft. - General Observation - MISSING TILES 100% 9:00 TO 3:00 START

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM

    3 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

    8.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CORRODED BEYOUND REBAR

  • Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    10.5 ft. - Surface Reinforcement Corroded, from 11 to 02 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES - LONG

    10.5 ft. - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES - LONG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUN & LONG

    49.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - CIRCUN & LONG

  • General Observation - 3 REMAINING TILES

    63.8 ft. - General Observation - 3 REMAINING TILES

  • General Observation - MISSING TILES 80%

    129.1 ft. - General Observation - MISSING TILES 80%

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

    203.7 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: YES, Start - LONG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

    205.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

    221.4 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM & LONG

  • Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: YES - LONG

    226.2 ft. - Surface Reinforcement Visible, at 03 o'clock, within 8 inches of joint: YES - LONG

  • Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES - LONG

    253.4 ft. - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: YES - LONG

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM

    399.2 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES - LONG

    405 ft. - Surface Reinforcement Visible, at 10 o'clock, within 8 inches of joint: YES - LONG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUN LONG

    441 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUN LONG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

    459.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCU & LONG

    464.3 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCU & LONG

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM

    529 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM

  • Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: NO - LONG

    556 ft. - Surface Reinforcement Visible, at 02 o'clock, within 8 inches of joint: NO - LONG

  • Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM LONG

    569 ft. - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO, Start - CIRCUM LONG

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES

    585.3 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM LONG CORRODED & BROKEN

    631.7 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: YES - CIRCUM LONG CORRODED & BROKEN

  • General Photograph - BROKEN REBAR

    633 ft. - General Photograph - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    655.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

Observations (43)

DistanceCodeObservation
662.2MGOMISSING TILES 100% FINISH
203.7SRCLONG
203.7SRC
405SRVLONG
662.2SAMSEVERE
464.3SRCCIRCU & LONG
662.2SRCCIRCUM
2SAMSEVERE
0AMH2:40AM
226.2SRVLONG
441SRCCIRCUN LONG
8.2SRCCORRODED BEYOUND REBAR
631.7SRCCIRCUM LONG CORRODED & BROKEN
10.5SRCLONG REBAR
221.4SRCCIRCUM & LONG
399.2SRCCIRCUM
8SRCCIRCUM
205.7SRC
459.5SRCCIRCUM
662.2SRCLONG
2MGOMISSING TILES 100% 9:00 TO 3:00 START
3SRCBROKEN CIRCUM
0MWL
556SRVLONG
580.4SRC
49.2SRCCIRCUN & LONG
10.5SRVLONG
662.2SRVCIRCUM LONG REBAR
63.8MGO3 REMAINING TILES
529SRCCIRCUM
253.4SRVLONG
633MGPBROKEN REBAR
569SRCCIRCUM LONG
205.7SRCCIRCUM
0MGOMH CONN ACTIVE 3:00
662.6AMH3:50AM
2SRVCIRCUM
585.3SRC
0MGOMH CONN ACTIVE 9:00
49.2SRCCORRODED BEYOUND REBAR
0MWM
655.5SRCBROKEN REBAR
129.1MGOMISSING TILES 80%

Properties (6)

custom_field_three
CORRODED-BROKEN REBAR
custom_field_two
1
customer
LACSD
datetime
2015-12-04T00:38:55-08:00
documentation
MARTIN,MANANES,REVELES
is_lateral_inspection
false