Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2015, 09:16 AM
  • 02 0123_02 0122_11172015_Manual.mp4

Date
11/17/2015
W/O
0541158
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02424
Time
1:16 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6639
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20151116MDM_DOWNEY_BELLFLOWER_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
02 0123
Downstream MH
02 0122
Dir. of Survey
Downstream
Length Surveyed
30.6 ft.
Total Length
30.6 ft.
Structural Index
4
Structural Quick
5436
Structural Rating
38
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
38
Pipe schematic from manhole 02 0123 to 02 0122
MH: 02 0123MH: 02 0122downstream0 ft. MGO - General Observation - MH CONN STUB 3:000 ft. MGO - General Observation - MH CONN STUB 9:000 ft. AMH - Upstream Manhole, Survey Begins - 3:40AM2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES2 ft. MGO - General Observation - MAG COAT 30% START2 ft. MGO - General Observation - MISSING TILES 50% START 8:00 TO 4:002.6 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM3.2 ft. MGO - General Observation - 10% MISSING TILES6.6 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM12.5 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish26.4 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM30.1 ft. MGO - General Observation - MISSING TILES 50%FINISH30.1 ft. MGP - General Photograph - NEW LINER DOWNSTREAM30.1 ft. MGO - General Observation - MAG COAT 30% FINISH30.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES30.6 ft. AMH - Downstream Manhole, Survey Ends - 3:50AM

Observation photos (9)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - MAG COAT 30% START

    2 ft. - General Observation - MAG COAT 30% START

  • General Observation - MISSING TILES 50% START 8:00 TO 4:00

    2 ft. - General Observation - MISSING TILES 50% START 8:00 TO 4:00

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM

    2.6 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM

  • General Observation - 10% MISSING TILES

    3.2 ft. - General Observation - 10% MISSING TILES

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

    6.6 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish

    12.5 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

    26.4 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

  • General Photograph - NEW LINER DOWNSTREAM

    30.1 ft. - General Photograph - NEW LINER DOWNSTREAM

Observations (16)

DistanceCodeObservation
0MGOMH CONN STUB 3:00
30.1MGOMISSING TILES 50%FINISH
30.1MGPNEW LINER DOWNSTREAM
2SAVSEVERE AGG AREAS OF MISSING TILES
30.1MGOMAG COAT 30% FINISH
30.6AMH3:50AM
2MGOMAG COAT 30% START
12.5SRV
2.6SRVLONG CIRCUM
2MGOMISSING TILES 50% START 8:00 TO 4:00
3.2MGO10% MISSING TILES
0MGOMH CONN STUB 9:00
30.1SAVSEVERE AGG AREAS OF MISSING TILES
0AMH3:40AM
26.4SRVCIRCUM
6.6SRVLONG CIRCUM

Properties (6)

custom_field_three
LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2015-11-17T01:16:42-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false