- Date
- 11/17/2015
- W/O
- 0541158
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00251
- PipeID
- P02425
- Time
- 1:15 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6639
- Sewer Name
- 02 DOWNEY-BELLFLOWER TRUNK
- City
- BELLFLOWER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 38
- Purpose
- Capital Improvement Program Assesment
- Project
- 20151116MDM_DOWNEY_BELLFLOWER_TRUNK
- Material
- RCP-CTL
- Shape
- Circular
- Height
- 33 in.
- Upstream MH
- 02 0124
- Downstream MH
- 02 0123
- Dir. of Survey
- Downstream
- Length Surveyed
- 32.9 ft.
- Total Length
- 32.9 ft.
- Structural Index
- 4
- Structural Quick
- 5336
- Structural Rating
- 33
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 4
- Overall Quick
- —
- Overall Rating
- 33
Pipe schematic from manhole 02 0124 to 02 0123 Observation photos (7)

2 ft. - General Observation - MAG COAT 30% START

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

2 ft. - General Observation - MISSING TILES 50% START 8:00 TO 4:00

2.3 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM

5.6 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM

8.4 ft. - General Photograph - 10% MISSING TILES

25.2 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG CIRCUM