Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 17, 2015, 09:14 AM
  • 02 0126_02 0125_11172015_Manual.mp4

Date
11/17/2015
W/O
0541158
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02427
Time
1:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6639
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20151116MDM_DOWNEY_BELLFLOWER_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
02 0126
Downstream MH
02 0125
Dir. of Survey
Downstream
Length Surveyed
305.5 ft.
Total Length
305.5 ft.
Structural Index
3
Structural Quick
533K
Structural Rating
198
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
198
Pipe schematic from manhole 02 0126 to 02 0125
MH: 02 0126MH: 02 0125downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:00AM2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES2 ft. MGO - General Observation - MISSING TILES 40% 8:00 TO 4:00 START2 ft. MGO - General Observation - MAG COAT 30% START12 ft. MGO - General Observation - MISSING TILES 20%45.6 ft. MGP - General Photograph108.3 ft. MGP - General Photograph122 ft. MGP - General Photograph192 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR240.6 ft. MGP - General Photograph273.9 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR292.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM305.2 ft. MGO - General Observation - MISSING TILES 40% FINISH305.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES305.2 ft. MGO - General Observation - MAG COAT 30% FINISH305.5 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (11)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AREAS OF MISSING TILES

  • General Observation - MISSING TILES 40% 8:00 TO 4:00 START

    2 ft. - General Observation - MISSING TILES 40% 8:00 TO 4:00 START

  • General Observation - MAG COAT 30% START

    2 ft. - General Observation - MAG COAT 30% START

  • General Observation - MISSING TILES 20%

    12 ft. - General Observation - MISSING TILES 20%

  • General Photograph

    45.6 ft. - General Photograph

  • General Photograph

    108.3 ft. - General Photograph

  • General Photograph

    122 ft. - General Photograph

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    192 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • General Photograph

    240.6 ft. - General Photograph

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    273.9 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

    292.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM

Observations (18)

DistanceCodeObservation
2SAVAREAS OF MISSING TILES
192SRVLONG & CIRCUM REBAR
273.9SRVCIRCUM REBAR
305.2MGOMISSING TILES 40% FINISH
0MWL
305.5AMH2:30AM
0MWM
122MGP
45.6MGP
108.3MGP
0AMH2:00AM
12MGOMISSING TILES 20%
2MGOMISSING TILES 40% 8:00 TO 4:00 START
305.2SAVSEVERE AGG AREAS OF MISSING TILES
240.6MGP
2MGOMAG COAT 30% START
305.2MGOMAG COAT 30% FINISH
292.9SRVCIRCUM

Properties (6)

custom_field_three
LONG CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2015-11-17T01:14:24-08:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false