- Date
- 11/16/2015
- W/O
- 0541158
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00251
- PipeID
- P02429
- Time
- 1:09 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G6639
- Sewer Name
- 02 DOWNEY-BELLFLOWER TRUNK
- City
- BELLFLOWER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 38
- Purpose
- Capital Improvement Program Assesment
- Project
- 20151116MDM_DOWNEY_BELLFLOWER_TRUNK
- Material
- RCP-CTL
- Shape
- Circular
- Height
- 33 in.
- Upstream MH
- 02 0128
- Downstream MH
- 02 0127
- Dir. of Survey
- Downstream
- Length Surveyed
- 342.5 ft.
- Total Length
- 342.5 ft.
- Structural Index
- 3
- Structural Quick
- 513M
- Structural Rating
- 209
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 209
Pipe schematic from manhole 02 0128 to 02 0127 Observation photos (9)

2 ft. - General Observation - MAG COAT 30% START 8:00 TO 4:00

2 ft. - General Observation - MISSING TILES 40% START 8:00 TO 4:00

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

28.9 ft. - Surface Reinforcement Visible, from 10 to 11 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

59.7 ft. - General Photograph - MISSING TILES 40%

71.3 ft. - General Observation - MISSING TILES 50%

95.1 ft. - General Observation - MISSING TILES 50% START

187.9 ft. - General Photograph - 50% MISSING TILES

322.2 ft. - General Observation - MISSING TILES 30% START