Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 16, 2015, 09:08 AM
  • 02 0129_02 0128_11162015_Manual.mp4

Date
11/16/2015
W/O
0541158
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02430
Time
1:08 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6638
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Capital Improvement Program Assesment
Project
20151116MDM_DOWNEY_BELLFLOWER_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
02 0129
Downstream MH
02 0128
Dir. of Survey
Downstream
Length Surveyed
346.6 ft.
Total Length
346.6 ft.
Structural Index
3
Structural Quick
553M
Structural Rating
232
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
234
Pipe schematic from manhole 02 0129 to 02 0128
MH: 02 0129MH: 02 0128downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES2 ft. MGO - General Observation - MISSING TILES 10% START2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 11 o'clock, , within 8 inches of joint: NO23.3 ft. MGO - General Observation - MISSING TILES 40%45.1 ft. MGO - General Observation - MISSING TILES 40%START58.7 ft. MGO - General Observation - MISSING TILES 50% START59.5 ft. MGO - General Observation - MAG COAT 40% 8:00 TO 4:00 START83.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE REBAR UNDER MAG COAT139.9 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR175.2 ft. MGP - General Photograph - 50% MISSING TILES208.6 ft. SRV - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR213.5 ft. SRV - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR276.5 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR346.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES346.1 ft. MGO - General Observation - MISSING TILES 50 FINISH346.1 ft. MGO - General Observation - MAG COAT 25% FINISH346.6 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (11)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - MISSING TILES 10% START

    2 ft. - General Observation - MISSING TILES 10% START

  • General Observation - MISSING TILES 40%

    23.3 ft. - General Observation - MISSING TILES 40%

  • General Observation - MISSING TILES 40%START

    45.1 ft. - General Observation - MISSING TILES 40%START

  • General Observation - MISSING TILES 50% START

    58.7 ft. - General Observation - MISSING TILES 50% START

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE REBAR UNDER MAG COAT

    83.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - POSSIBLE REBAR UNDER MAG COAT

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    139.9 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • General Photograph - 50% MISSING TILES

    175.2 ft. - General Photograph - 50% MISSING TILES

  • Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    208.6 ft. - Surface Reinforcement Visible, from 01 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    213.5 ft. - Surface Reinforcement Visible, from 12 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    276.5 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

Observations (21)

DistanceCodeObservation
58.7MGOMISSING TILES 50% START
2SAVSEVERE AGG AREAS OF MISSING TILES
139.9SRVCIRCUM REBAR
83.7SRVPOSSIBLE REBAR UNDER MAG COAT
59.5MGOMAG COAT 40% 8:00 TO 4:00 START
2.3DAGS
213.5SRVCIRCUM REBAR
346.1SAVSEVERE AGG AREAS OF MISSING TILES
208.6SRVCIRCUM REBAR
346.1MGOMISSING TILES 50 FINISH
346.1MGOMAG COAT 25% FINISH
175.2MGP50% MISSING TILES
23.3MGOMISSING TILES 40%
276.5SRVCIRCUM REBAR
0MWM
45.1MGOMISSING TILES 40%START
346.6AMH4:45AM
0MGOMH CONN ACTIVE 3:00
0AMH4:10AM
0MWL
2MGOMISSING TILES 10% START

Properties (6)

custom_field_three
CIRCUM REBAR
custom_field_two
2
customer
LACSD
datetime
2015-11-16T01:08:14-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false