Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 13, 2015, 10:59 AM
  • 02 0135_02 0134_11132015_Manual.mp4

Date
11/13/2015
W/O
0536410
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00251
PipeID
P02437
Time
2:59 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6636
Sewer Name
02 DOWNEY-BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
20151112MDM_DOWNEY_BELLFLOWER_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Upstream MH
02 0135
Downstream MH
02 0134
Dir. of Survey
Downstream
Length Surveyed
295.9 ft.
Total Length
295.9 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
81
Pipe schematic from manhole 02 0135 to 02 0134
MH: 02 0135MH: 02 0134downstream0 ft. MGO - General Observation - MH CONN ACTIVE 3:000 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:25AM28.8 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - HAIRLINE37.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE40.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB42.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES89.6 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB92.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB117.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start138.8 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB141.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB188 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE191.1 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN214.9 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE237.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6" - STUB240.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB244.8 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE284.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 6" - OPEN290.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN292.6 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6" - STUB295.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish295.9 ft. AMH - Downstream Manhole, Survey Ends - 3:50AM

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    117.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
240.2TFCSTUB
89.6TFCSTUB
0MGOMH CONN ACTIVE 3:00
284.6TBOPEN
40.6TFCSTUB
295.5DAGS
28.8FLHAIRLINE
244.8FCHAIRLINE
0MWL
191.1TFOPEN
42.6CL
292.6TFCSTUB
295.9AMH3:50AM
138.8TFCSTUB
0MWM
117.6DAGS
237.3TFCSTUB
214.9FCHAIRLINE
141.8TFCSTUB
37.5TFACTIVE
188TFACTIVE
290.3TFOPEN
92.6TFCSTUB
0AMH3:25AM

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2015-11-13T02:59:44-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false