Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 09:26 PM
Date
11/06/2015
W/O
0530843
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00643
PipeID
P13331
Time
1:26 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6626
Sewer Name
16 ALMANSOR STREET EXTENSION TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
04
Purpose
Routine Assessment
Project
20151105AM_ALMANSOR_STREET_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 0281
Downstream MH
B 0490
Dir. of Survey
Downstream
Length Surveyed
45.8 ft.
Total Length
45.8 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
22
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
22
Pipe schematic from manhole 02 0281 to B 0490
MH: 02 0281MH: B 0490downstream0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:28 PM0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK2.1 ft. CC - Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: NO4.2 ft. CM - Crack Multiple, from 07 to 01 o'clock, within 8 inches of joint: NO4.2 ft. BSV - Broken Soil Visible, at 01 o'clock, within 8 inches of joint: NO10.1 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES34.3 ft. CM - Crack Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES38.9 ft. CM - Crack Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES45.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES45.3 ft. MMC - Material Change, Other (state in comments) - CONCRETE PIPE45.3 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH45.5 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK45.5 ft. MGO - General Observation - ROACHES INSIDE THE MH.45.8 ft. AMH - Downstream Manhole, Survey Ends - 1:41 PM

Observation photos (6)

  • Upstream Manhole, Survey Begins - 1:28 PM

    0 ft. - Upstream Manhole, Survey Begins - 1:28 PM

  • Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: NO

    2.1 ft. - Crack Circumferential, from 01 to 05 o'clock, within 8 inches of joint: NO

  • Broken Soil Visible, at 01 o'clock, within 8 inches of joint: NO

    4.2 ft. - Broken Soil Visible, at 01 o'clock, within 8 inches of joint: NO

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    10.1 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    45.3 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Material Change, Other (state in comments) - CONCRETE PIPE

    45.3 ft. - Material Change, Other (state in comments) - CONCRETE PIPE

Observations (17)

DistanceCodeObservation
4.2CM
45.3FL
38.9CM
45.3MMCCONCRETE PIPE
45.8AMH1:41 PM
10.1FM
45.5MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK
0MGOROACHES INSIDE THE MH.
45.5MGOROACHES INSIDE THE MH.
45.3MGOSLIGHT GREASE THROUGHOUT THE REACH
0MWM
34.3CM
4.2BSV
0AMH1:28 PM
2.1CC
0MWL
0MGOACTIVE CONN. INSIDE THE MH. @ 09 O'CLOCK

Properties (6)

custom_field_three
HOLE IN THE PIPE
custom_field_two
1
customer
LACSD
datetime
2015-11-06T13:26:46-08:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection
false