Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 08:45 PM
  • 16 0283_16 0282_11062015_Manual.mp4

Date
11/06/2015
W/O
0530843
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00643
PipeID
P13333
Time
12:45 PM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6626
Sewer Name
16 ALMANSOR STREET EXTENSION TRUNK
City
ALHAMBRA
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
04
Purpose
Routine Assessment
Project
20151105AM_ALMANSOR_STREET_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
16 0283
Downstream MH
16 0282
Dir. of Survey
Downstream
Length Surveyed
241.1 ft.
Total Length
241.1 ft.
Structural Index
2
Structural Quick
3124
Structural Rating
11
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 16 0283 to 16 0282
MH: 16 0283MH: 16 0282downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:48 PM0 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 06 O'CLOCK0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MGO - General Observation - ROACHES INSIDE THE MH.58.2 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES66 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES155.1 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES207.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES223.6 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES239.6 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH239.8 ft. MGO - General Observation - ROACHES INSIDE THE MH.241.1 ft. AMH - Downstream Manhole, Survey Ends - 1:01 PM

Observation photos (2)

  • Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

    58.2 ft. - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    155.1 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0MWM
0AMH12:48 PM
239.8MGOROACHES INSIDE THE MH.
241.1AMH1:01 PM
155.1CM
58.2FC
223.6CL
0MGOACTIVE CONN. INSIDE THE MH. @ 06 O'CLOCK
0MWL
0MGOROACHES INSIDE THE MH.
207.5CL
66CL
239.6MGOSLIGHT GREASE THROUGHOUT THE REACH

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-11-06T12:45:52-08:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection
false