Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2015, 05:45 PM
  • 16 0285_16 0284_11062015_Manual.mp4

Date
11/06/2015
W/O
0530843
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00643
PipeID
P13335
Time
9:45 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6626
Sewer Name
16 ALMANSOR STREET EXTENSION TRUNK
City
ALHAMBRA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
25
Purpose
Routine Assessment
Project
20151105AM_ALMANSOR_STREET_EXTENSION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
16 0285
Downstream MH
16 0284
Dir. of Survey
Downstream
Length Surveyed
346 ft.
Total Length
346 ft.
Structural Index
2
Structural Quick
3223
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 16 0285 to 16 0284
MH: 16 0285MH: 16 0284downstream0 ft. MGO - General Observation - ROACHES INSIDE THE MH.0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 9:46 AM26.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES86.4 ft. MGO - General Observation - CHIPPING FROM 01 TO 02 O'CLOCK163 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES175.2 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES263.6 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES320 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES344 ft. MGO - General Observation - SLIGHT GREASE THROUGHOUT THE REACH344.3 ft. MGO - General Observation - ROACHES INSIDE THE MH.346 ft. AMH - Downstream Manhole, Survey Ends - 10:06 AM

Observation photos (2)

  • General Observation - CHIPPING FROM 01 TO 02 O'CLOCK

    86.4 ft. - General Observation - CHIPPING FROM 01 TO 02 O'CLOCK

  • Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

    163 ft. - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
320CL
175.2CL
344MGOSLIGHT GREASE THROUGHOUT THE REACH
344.3MGOROACHES INSIDE THE MH.
0MGOROACHES INSIDE THE MH.
163FC
263.6CM
0MWM
0MWL
26.3CM
346AMH10:06 AM
86.4MGOCHIPPING FROM 01 TO 02 O'CLOCK
0AMH9:46 AM

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2015-11-06T09:45:36-08:00
documentation
MIRANDA, FRANKLIN, SHADLER
is_lateral_inspection