Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2021, 09:28 AM
  • 01 1175_01 1174A_03302021_023908.mp4

Date
03/30/2021
W/O
886342
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02027
Time
2:28 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8708
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
WO_886342_TV01072_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
01 1175
Downstream MH
01 1174A
Dir. of Survey
Downstream
Length Surveyed
93 ft.
Total Length
93 ft.
Structural Index
3
Structural Quick
413C
Structural Rating
58
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
58
Pipe schematic from manhole 01 1175 to 01 1174A
MH: 01 1175MH: 01 1174Adownstream0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11750 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"9.3 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES70.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"93 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish93 ft. AMH - Downstream Manhole, Survey Ends - 01 1174A93 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    9.3 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 9 OC'LOCK
70.1TF
93SAV
93AMH01 1174A
0MWM
93MGOCONNECTION AT THE MH 3 OC'LOCK
2.1SAV
0AMH01 1175
72.5TF
7.7TF
0MWL
9.3FM

Properties (7)

additional_info
630074032921202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-03-30T02:28:38-07:00
documentation
PROPIPE
is_lateral_inspection
false