Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2021, 07:45 AM
  • 01 1172_01 1171_03312021_005003.mp4

Date
03/31/2021
W/O
886342
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02023
Time
12:45 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8711
Sewer Name
01 WILCOX AVENUE TRUNK
City
CUDAHY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
WO_886342_TV01072_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1172
Downstream MH
01 1171
Dir. of Survey
Downstream
Length Surveyed
37 ft.
Total Length
37 ft.
Structural Index
3
Structural Quick
5537
Structural Rating
58
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
58
Pipe schematic from manhole 01 1172 to 01 1171
MH: 01 1172MH: 01 1171downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11720 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15 ft. B - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES18 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES20 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - possible broken pipe, contractor did not stop36 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - possible brokn pipe, contractor did not stop37 ft. AMH - Downstream Manhole, Survey Ends - 01 117237 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK37 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish37 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

    15 ft. - Broken, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

    18 ft. - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
0AMH01 1172
15B
18B
37AMH01 1172
37MGOCONNECTION AT THE MH 9 OC'LOCK
2.1SAV
37SAV
0MGOCONNECTION AT THE MH 9 OC'LOCK
20Bpossible broken pipe, contractor did not stop
0MWL
37SSS
0MWM
36Bpossible brokn pipe, contractor did not stop
0MGOCONNECTION AT THE MH 3 OC'LOCK
8.1SSS

Properties (7)

additional_info
630074033021203
custom_field_three
AGGREGATE VISIBLE/SPALLING/BROKEN PIPE
custom_field_two
1
customer
1
datetime
2021-03-31T00:45:55-07:00
documentation
PROPIPE
is_lateral_inspection
false