- Date
- 03/30/2021
- W/O
- 886342
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00225
- PipeID
- P02002
- Time
- 10:48 PM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8711
- Sewer Name
- 01 WILCOX AVENUE TRUNK
- City
- CUDAHY
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 11
- Purpose
- Routine Assessment
- Project
- WO_886342_TV01072_APR2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 15 in.
- Upstream MH
- 01 1152
- Downstream MH
- 01 1151
- Dir. of Survey
- Downstream
- Length Surveyed
- 262.6 ft.
- Total Length
- 262.6 ft.
- Structural Index
- 3
- Structural Quick
- 3I2I
- Structural Rating
- 258
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 258
Pipe schematic from manhole 01 1152 to 01 1151 Observation photos (3)

3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

3.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

153.8 ft. - Tap Saddle, at 11 o'clock, -, within 8 inches of joint: NO, 6"