Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2021, 04:11 AM
  • C 0387_C 0386_04142021_213420.mp4

Date
04/14/2021
W/O
886022
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00142
PipeID
P09851
Time
9:11 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8728
Sewer Name
C JOINT OUTFALL C - UNIT 8D
City
LAKEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_886022_TV19067_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
114 in.
Upstream MH
C 0387
Downstream MH
C 0386
Dir. of Survey
Downstream
Length Surveyed
530.1 ft.
Total Length
530.1 ft.
Structural Index
3
Structural Quick
5T3T
Structural Rating
1060
O&M Index
3
O&M Quick
423G
O&M Rating
132
Overall Index
3
Overall Quick
Overall Rating
1192
Pipe schematic from manhole C 0387 to C 0386
MH: C 0387MH: C 0386downstream0 ft. AMH - Upstream Manhole, Survey Begins - C 03870 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.3 ft. ID - Infiltration Dripper, from 08 to 04 o'clock, within 8 inches of joint: YES, Start126.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197 ft. ID - Infiltration Dripper, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.5 ft. IW - Infiltration Weeper, from 12 to 02 o'clock, within 8 inches of joint: YES404.2 ft. ID - Infiltration Dripper, at 09 o'clock, within 8 inches of joint: YES438.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"443.9 ft. IR - Infiltration Runner, from 02 to 04 o'clock, within 8 inches of joint: YES500.5 ft. IW - Infiltration Weeper, from 02 to 03 o'clock, within 8 inches of joint: YES514.6 ft. DAE - Deposits Attached Encrustation, 15 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES514.6 ft. IR - Infiltration Runner, at 08 o'clock, within 8 inches of joint: YES530 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish530.1 ft. AMH - Downstream Manhole, Survey Ends - C 0386530.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish530.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (9)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Dripper, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.3 ft. - Infiltration Dripper, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Weeper, from 12 to 02 o'clock, within 8 inches of joint: YES

    356.5 ft. - Infiltration Weeper, from 12 to 02 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, at 09 o'clock, within 8 inches of joint: YES

    404.2 ft. - Infiltration Dripper, at 09 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, from 02 to 04 o'clock, within 8 inches of joint: YES

    443.9 ft. - Infiltration Runner, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Weeper, from 02 to 03 o'clock, within 8 inches of joint: YES

    500.5 ft. - Infiltration Weeper, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 15 %of cross sectional area, from 03 to 05 o'clock,  , within 8 inches of joint: YES

    514.6 ft. - Deposits Attached Encrustation, 15 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES

  • Infiltration Runner, at 08 o'clock, within 8 inches of joint: YES

    514.6 ft. - Infiltration Runner, at 08 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
126.4TF
2.2SAP
530.1AMHC 0386
438.9TF
356.5IW
530.1SAP
404.2ID
0AMHC 0387
500.5IW
0MWM
514.6DAE
0MWL
530SSS
443.9IR
197ID
530.1SRV
2.2SSS
8.3ID
514.6IR
2.2SRV

Properties (8)

additional_info
630074041421201
custom_field_three
AGGREGATE PROJECTING/REINFORCEMENT VISIBLE/INFILTR
custom_field_two
2
customer
1
datetime
2021-04-14T21:11:22-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26643