Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 20, 2021, 08:32 AM
  • 02 0748_02 0850_04202021_013704.mp4

Date
04/20/2021
W/O
886157
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00296
PipeID
P03417
Time
1:32 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8736
Sewer Name
02 OLD RIVER SCHOOL ROAD RELIEF TRUNK, SECTION 1
City
DOWNEY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
WO_886157_TV02088_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
15 in.
Upstream MH
02 0748
Downstream MH
02 0850
Dir. of Survey
Downstream
Length Surveyed
14.4 ft.
Total Length
14.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0748 to 02 0850
MH: 02 0748MH: 02 0850downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 07480 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start13.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish14.4 ft. AMH - Downstream Manhole, Survey Ends - 02 085014.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
14.4AMH02 0850
2.1MGOMAG COAT
0MWM
0AMH02 0748
14.4MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
2.1SAV
13.8SAV

Properties (7)

additional_info
630074041921202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-04-20T01:32:39-07:00
documentation
PROPIPE
is_lateral_inspection
false