Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2021, 04:13 AM
  • 01 0780_01 0778_03302021_212306.mp4

Date
03/30/2021
W/O
885805
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00197
PipeID
P01480
Time
9:13 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8709
Sewer Name
01 BULLIS ROAD-TEMPLE STREET TRUNK
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_885805_TV01275_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
36 in.
Upstream MH
01 0780
Downstream MH
01 0778
Dir. of Survey
Downstream
Length Surveyed
173.6 ft.
Total Length
173.6 ft.
Structural Index
3
Structural Quick
423F
Structural Rating
107
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
107
Pipe schematic from manhole 01 0780 to 01 0778
MH: 01 0780MH: 01 0778downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 07800 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 25 %of cross sectional area3.1 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES6.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.1 ft. FM - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES83.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0778173.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    3.1 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    21.1 ft. - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
21.1FM
3.1FM
173.6AMH01 0778
0AMH01 0780
0MWM
134.7TFC
173.6CM
0MGOCONNECTION AT THE MH 9 OC'LOCK
6.4CM
83.9TFC
0MWL

Properties (7)

additional_info
630074033021201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-30T21:13:54-07:00
documentation
PROPIPE
is_lateral_inspection
false