Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2021, 09:30 AM
  • 14 0511_14 0510_04082021_024401.mp4

Date
04/08/2021
W/O
886053
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00579
PipeID
P18602
Time
2:30 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8773
Sewer Name
14 TRUNK "C"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
19
Purpose
Routine Assessment
Project
WO_886053_TV14020_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0511
Downstream MH
14 0510
Dir. of Survey
Downstream
Length Surveyed
380.5 ft.
Total Length
380.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 14 0511 to 14 0510
MH: 14 0511MH: 14 0510downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 05110 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"33.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"108.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.2 ft. CS - Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES234.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"259 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"284.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"330.3 ft. MWL - Water Level, 50 %of cross sectional area340.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"365.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"378.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish380.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0510

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

    232.2 ft. - Crack Spiral, from 12 to 02 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
0AMH14 0511
330.3MWL
309.5TFC
232.2CS
209.2TFC
8TFC
380.5AMH14 0510
378.4DAGS
57.7TFC
365.2TFC
83.8TFC
2DAGS
340.1TFC
284.2TFC
234.6TFC
183.8TFC
0MWL
108.5TFC
33.5TFC
0MWM
158.8TFC
259TFC
134.1TFC

Properties (7)

additional_info
630069040721201
custom_field_three
MINOR CRACKS
custom_field_two
4
customer
1
datetime
2021-04-08T02:30:10-07:00
documentation
PRO PIPE
is_lateral_inspection
false