Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2021, 08:40 AM
  • 14 0515_14 0514A_04082021_015003.mp4

Date
04/08/2021
W/O
886053
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00579
PipeID
P24665
Time
1:40 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8773
Sewer Name
14 TRUNK "C"
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
19
Purpose
Routine Assessment
Project
WO_886053_TV14020_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0515
Downstream MH
14 0514A
Dir. of Survey
Downstream
Length Surveyed
154.7 ft.
Total Length
154.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
512F
O&M Rating
73
Overall Index
2
Overall Quick
Overall Rating
73
Pipe schematic from manhole 14 0515 to 14 0514A
MH: 14 0515MH: 14 0514Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 05150 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 75 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start12.8 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start12.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"32 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish64.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"89.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish154.7 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK154.7 ft. AMH - Downstream Manhole, Survey Ends - 14 0514A

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    12.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0AMH14 0515
12.8DAGS
89.7TFC
154.7MGOCONNECTION AT MH 3 O'CLOCK
154.7AMH14 0514A
12.8TFA
140.6TFC
64.9TFC
32DAGS
153.4DAGS
115.2TFC
0MWL
0MWM
2DAGS

Properties (7)

additional_info
630069040721201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-04-08T01:40:17-07:00
documentation
PRO PIPE
is_lateral_inspection
false