Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 7, 2021, 05:59 AM
  • 14 0826_14 0825_04062021_230945.mp4

Date
04/06/2021
W/O
886053
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00579
PipeID
P20709
Time
10:59 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8772
Sewer Name
14 TRUNK "C"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
19
Purpose
Routine Assessment
Project
WO_886053_TV14020_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 0826
Downstream MH
14 0825
Dir. of Survey
Downstream
Length Surveyed
315.1 ft.
Total Length
315.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2S00
O&M Rating
202
Overall Index
2
Overall Quick
Overall Rating
202
Pipe schematic from manhole 14 0826 to 14 0825
MH: 14 0826MH: 14 0825downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 08262 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start118.8 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS313.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish313.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish315.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE315.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0825315.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    315.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (10)

DistanceCodeObservation
0MWM
313.1DAGS
315.1MGOCOCKROACHES IN MANHOLE
315.1AMH14 0825
0MWL
0AMH14 0826
313.1DSZ
315.1MGOCONNECTION AT MH 9 O'CLOCK
118.8DSZDEBRIS
2DAGS

Properties (7)

additional_info
630069040621201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-04-06T22:59:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false