Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2021, 08:23 AM
  • 14 0516_14 0515_04082021_013956.mp4

Date
04/08/2021
W/O
886053
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00579
PipeID
P18607
Time
1:23 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8773
Sewer Name
14 TRUNK "C"
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
19
Purpose
Routine Assessment
Project
WO_886053_TV14020_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0516
Downstream MH
14 0515
Dir. of Survey
Downstream
Length Surveyed
380.4 ft.
Total Length
380.4 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
5141
O&M Rating
211
Overall Index
2
Overall Quick
Overall Rating
217
Pipe schematic from manhole 14 0516 to 14 0515
MH: 14 0516MH: 14 0515downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 05162 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"44.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"69.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"115.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.2 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"250 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS267.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"293.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"334.4 ft. MWM - Water Mark, 75 %of cross sectional area334.4 ft. MWL - Water Level, 50 %of cross sectional area337.6 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES344.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"367.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES373.6 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6", 6"378.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish378.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish380.4 ft. AMH - Downstream Manhole, Survey Ends - 14 0515

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    337.6 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    367.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
167.2TBA
217.1TFC
334.4MWM
115.1TFC
378.1DSZ
243.2TFC
0MWM
337.6CM
0MWL
166TFC
94.9TFC
373.6TBA
69.8TFC
2DAGS
0AMH14 0516
334.4MWL
140.8TFC
44.7TFC
318.9TFC
380.4AMH14 0515
267.8TFC
378.1DAGS
344.5TFC
367.6CM
191.4TFC
250DSZDEBRIS
293.8TFC
18.3TFC

Properties (7)

additional_info
630069040721201
custom_field_three
MINOR CRACKS
custom_field_two
4
customer
1
datetime
2021-04-08T01:23:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false