Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2021, 09:53 AM
  • 14 0882_14 0881_04022021_030504.mp4

Date
04/02/2021
W/O
886053
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00579
PipeID
P22357
Time
2:53 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8767
Sewer Name
14 TRUNK "C"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
24
Purpose
Routine Assessment
Project
WO_886053_TV14020_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0882
Downstream MH
14 0881
Dir. of Survey
Downstream
Length Surveyed
331.1 ft.
Total Length
331.1 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
2L00
O&M Rating
132
Overall Index
2
Overall Quick
Overall Rating
136
Pipe schematic from manhole 14 0882 to 14 0881
MH: 14 0882MH: 14 0881downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 08822 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start117.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES166.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES329.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0881

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    117.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    166.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
117.6CL
2DAGS
0MWL
166.3CL
0MWM
329.6DAGS
0AMH14 0882
331.1AMH14 0881

Properties (7)

additional_info
630069040121231
custom_field_three
MINOR CRACKS
custom_field_two
4
customer
1
datetime
2021-04-02T02:53:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false