Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 20, 2021, 04:42 AM
  • 03 0276A_03 0276_04192021_215435.mp4

Date
04/19/2021
W/O
887811
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00385
PipeID
P04880
Time
9:42 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8735
Sewer Name
03 MARKET STREET TRUNK
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
07
Purpose
Routine Assessment
Project
CA_WO_887811
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
27 in.
Upstream MH
03 0276A
Downstream MH
03 0276
Dir. of Survey
Downstream
Length Surveyed
97.9 ft.
Total Length
97.9 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
57
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
57
Pipe schematic from manhole 03 0276A to 03 0276
MH: 03 0276AMH: 03 0276downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 0276A0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK3.1 ft. CM - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES5.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"85.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"97.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish97.8 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK97.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK97.9 ft. AMH - Downstream Manhole, Survey Ends - 03 0276

Observation photos (2)

  • Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    3.1 ft. - Crack Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0MWL
90.3TFC
40.5TFC
97.9MGOCONNECTION AT THE MH 3 OC'LOCK
0AMH03 0276A
97.8CM
0MWM
38.3TFC
97.8MGOCONNECTION AT THE MH 9 OC'LOCK
85.3TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
5.9CM
3.1CM
97.9AMH03 0276

Properties (7)

additional_info
630074041921201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-04-19T21:42:43-07:00
documentation
PRO PIPE
is_lateral_inspection
false