Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 15, 2021, 10:02 AM
  • 03 0265A_03 0265_04152021_033505.mp4

Date
04/15/2021
W/O
887811
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00385
PipeID
P04868
Time
3:02 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8836
Sewer Name
03 MARKET STREET TRUNK
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
07
Purpose
Routine Assessment
Project
CA_WO_887811
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
03 0265A
Downstream MH
03 0265
Dir. of Survey
Downstream
Length Surveyed
351.3 ft.
Total Length
351.3 ft.
Structural Index
2
Structural Quick
2800
Structural Rating
16
O&M Index
2
O&M Quick
2500
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
26
Pipe schematic from manhole 03 0265A to 03 0265
MH: 03 0265AMH: 03 0265downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 0265A56.8 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"120.1 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"188.8 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"193 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8"199.1 ft. CS - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES215 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES235.1 ft. CS - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES252.1 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"278.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES286.8 ft. CS - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES290.6 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES316 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"317.5 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES342.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES351.3 ft. AMH - Downstream Manhole, Survey Ends - 03 0265

Observation photos (14)

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

    56.8 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

    120.1 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

    188.8 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8"

    193 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 8"

  • Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

    199.1 ft. - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    215 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    235.1 ft. - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

    252.1 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    278.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

    286.8 ft. - Crack Spiral, from 01 to 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    290.6 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

    316 ft. - Tap Break-In Intruding, at 12 o'clock, -, -, within 8 inches of joint: YES, 10", 1"

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    317.5 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    342.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
215CL
199.1CS
235.1CS
0MWM
56.8TBI
188.8TBI
0MGOCONNECTION AT MH 3 O'CLOCK
342.1CL
120.1TBI
351.3AMH03 0265
0MWL
193TB
278.3CL
316TBI
0AMH03 0265A
252.1TBI
317.5CL
286.8CS
290.6CL

Properties (6)

custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-04-15T03:02:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false