Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2021, 09:34 AM
  • 05 2671_05 0637_04132021_025051.mp4

Date
04/13/2021
W/O
887823
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00509
PipeID
P05864
Time
2:34 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8828
Sewer Name
05 PRAIRIE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
05
Purpose
Routine Assessment
Project
CA_WO_887823
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
10 in.
Upstream MH
05 2671
Downstream MH
05 0637
Dir. of Survey
Downstream
Length Surveyed
418.3 ft.
Total Length
418.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
150
Pipe schematic from manhole 05 2671 to 05 0637
MH: 05 2671MH: 05 0637downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 26710 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area17.6 ft. LL - Alignment Left, 20 %, Start36.4 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES, Start101.3 ft. LL - Alignment Left, 20 %, Finish327.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 12"327.4 ft. DAE - Deposits Attached Encrustation, 10 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES, Finish418.2 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK418.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0637

Observation photos (2)

  • Alignment Left, 20 %, Start

    17.6 ft. - Alignment Left, 20 %, Start

  • Deposits Attached Encrustation, 10 %of cross sectional area, at 04 o'clock,  , within 8 inches of joint: YES, Start

    36.4 ft. - Deposits Attached Encrustation, 10 %of cross sectional area, at 04 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMH05 2671
0MGOCONNECTION AT MH, 3 O'CLOCK
418.2MGOCONNECTION AT MH, 3 O'CLOCK
327.4TF
0MWL
17.6LL
101.3LL
0MWM
418.3AMH05 0637
327.4DAE
36.4DAE

Properties (6)

custom_field_three
NO STRUCTURAL DEFECTS
custom_field_two
4
customer
1
datetime
2021-04-13T02:34:11-07:00
documentation
PRO PIPE
is_lateral_inspection
false