Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 12, 2021, 10:07 AM
  • C 0305_C 0304_04122021_032419.mp4

Date
04/12/2021
W/O
885817
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00134
PipeID
P09765
Time
3:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8726
Sewer Name
C JOINT OUTFALL C - UNIT 6E
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_885817_TV19035_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
21 in.
Upstream MH
C 0304
Downstream MH
C 0305
Dir. of Survey
Upstream
Length Surveyed
452.3 ft.
Total Length
452.3 ft.
Structural Index
2
Structural Quick
2Q00
Structural Rating
178
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
180
Pipe schematic from manhole C 0304 to C 0305
MH: C 0304MH: C 0305upstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Ends - C 03053.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"172.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"269 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"300.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 07 to 12 o'clock, , within 8 inches of joint: YES317.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"325 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"365.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"373.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"413.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"421.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"449.4 ft. MGO - General Observation - MAG COAT449.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start452.3 ft. MWM - Water Mark, 25 %of cross sectional area452.3 ft. MWL - Water Level, 15 %of cross sectional area452.3 ft. AMH - Downstream Manhole, Survey Begins - C 0304

Observations (27)

DistanceCodeObservation
287.5TFC
280.1TFC
152DAE
335.8TFC
2.9MGOMAG COAT
384.1TFC
327.6TFC
86.8TFC
231.2TFC
183.3TFC
30.6TFC
0MWM
223.2TFC
135.2TFC
449SSS
423.5TFC
391.8TFC
452.3MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
127.3TFC
38.9TFC
431.9TFC
0AMHC 0304
452.3AMHC 0305
79TFC
2.5SSS
175.2TFC

Properties (7)

additional_info
630074041221001
custom_field_three
ENCRUSTATION
custom_field_two
3
customer
1
datetime
2021-04-12T03:07:49-07:00
documentation
PROPIPE
is_lateral_inspection
false