Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2021, 08:04 AM
  • C 0299_C 0298_04132021_013411.mp4

Date
04/13/2021
W/O
885817
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00134
PipeID
P09759
Time
1:04 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8727
Sewer Name
C JOINT OUTFALL C - UNIT 6E
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_885817_TV19035_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
C 0298
Downstream MH
C 0299
Dir. of Survey
Upstream
Length Surveyed
714.8 ft.
Total Length
714.8 ft.
Structural Index
2
Structural Quick
2[00
Structural Rating
284
O&M Index
2
O&M Quick
322Y
O&M Rating
266
Overall Index
2
Overall Quick
Overall Rating
550
Pipe schematic from manhole C 0298 to C 0299
MH: C 0298MH: C 0299upstream0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: NO, Finish0 ft. AMH - Downstream Manhole, Survey Ends - C 02982.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish20.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"28.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"85 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"133.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"181.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"229.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"277.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"286 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"323.9 ft. ID - Infiltration Dripper, from 12 to 01 o'clock, within 8 inches of joint: NO326.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"334.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"361.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"369.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"401.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"409.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"441.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"449.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"487.7 ft. ID - Infiltration Dripper, from 12 to 01 o'clock, within 8 inches of joint: NO489.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"497.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"537.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"545.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"586.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"594.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"642.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"648.7 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: NO, Start650.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"690.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"698.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"710.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start710.6 ft. MGO - General Observation - MAG COAT714.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK714.8 ft. MWL - Water Level, 15 %of cross sectional area714.8 ft. MWM - Water Mark, 25 %of cross sectional area714.8 ft. AMH - Downstream Manhole, Survey Begins - C 0298

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: NO, Start

    66.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: NO, Start

  • Infiltration Dripper, from 12 to 01 o'clock, within 8 inches of joint: NO

    227.1 ft. - Infiltration Dripper, from 12 to 01 o'clock, within 8 inches of joint: NO

Observations (42)

DistanceCodeObservation
581.2TFC
128.4TFC
345.4TFC
388.7TFC
227.1ID
72.5TFC
714.8DAE
390.9ID
4.2MGOMAG COAT
714.8AMHC 0298
313TFC
273TFC
176.9TFC
428.8TFC
437TFC
265TFC
712SSS
629.8TFC
120.5TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK
0MWL
168.9TFC
0MWM
493.3TFC
224.9TFC
305.4TFC
16.6TFC
24.4TFC
589.7TFC
638TFC
216.9TFC
353.4TFC
541.5TFC
64.1TFC
380.7TFC
685.9TFC
694.1TFC
4.5SSS
485.2TFC
66.1DAE
533.1TFC
0AMHC 0298

Properties (7)

additional_info
630074041221201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-04-13T01:04:22-07:00
documentation
PROPIPE
is_lateral_inspection
false