Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2021, 06:36 AM
  • C 0297_C 0296_04122021_234837.mp4

Date
04/12/2021
W/O
885817
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00134
PipeID
P09757
Time
11:36 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8727
Sewer Name
C JOINT OUTFALL C - UNIT 6E
City
LAKEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_885817_TV19035_APR2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
27 in.
Upstream MH
C 0297
Downstream MH
C 0296
Dir. of Survey
Downstream
Length Surveyed
257.9 ft.
Total Length
257.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
322B
O&M Rating
36
Overall Index
2
Overall Quick
Overall Rating
36
Pipe schematic from manhole C 0297 to C 0296
MH: C 0297MH: C 0296downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 02970 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK2.1 ft. MGO - General Observation - MAG COAT36.5 ft. ID - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES47.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"48.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"181.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start197 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: NO200.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"208.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish257.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK257.9 ft. AMH - Downstream Manhole, Survey Ends - C 0296

Observation photos (3)

  • Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

    36.5 ft. - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    181.6 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: NO

    197 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: NO

Observations (21)

DistanceCodeObservation
0MWM
144.8TFC
0MWL
248.6TFC
104.9TFC
47.7TFC
200.7TFC
181.6DAE
56.2TFC
197ID
152.8TFC
257.9MGOCONNECTION AT THE MH 3 OC'LOCK
0AMHC 0297
48.9TFA
96.1TFC
257.9AMHC 0296
0MGOCONNECTION AT THE MH 3 OC'LOCK
208.9TFC
257.8DAE
36.5ID
2.1MGOMAG COAT

Properties (7)

additional_info
630074041221201
custom_field_three
ENCRUSTATION
custom_field_two
3
customer
1
datetime
2021-04-12T23:36:01-07:00
documentation
PROPIPE
is_lateral_inspection
false