- Date
- 04/29/2021
- W/O
- 0879983
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00057
- PipeID
- P11485
- Time
- 12:51 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H1789
- Sewer Name
- J JOINT OUTFALL J - UNIT 1E
- City
- PALOS VERDES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 46
- Purpose
- Capital Improvement Program Assesment
- Project
- 20210428MDM_JOINT_OUTFALL_J_UNIT_1E
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 27 in.
- Upstream MH
- J 0239
- Downstream MH
- J 0238
- Dir. of Survey
- Downstream
- Length Surveyed
- 43.8 ft.
- Total Length
- 43.8 ft.
- Structural Index
- 3
- Structural Quick
- 4122
- Structural Rating
- 8
- O&M Index
- 4
- O&M Quick
- 4100
- O&M Rating
- 4
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 12
Pipe schematic from manhole J 0239 to J 0238 Observation photos (4)

2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

18.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE

29.7 ft. - Water Mark, 20 %of cross sectional area