Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2021, 09:40 AM
  • 30 0069_30 0068_532021_024444.mp4

Date
05/03/2021
W/O
0886345
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00878
PipeID
P17772
Time
2:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1795
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
HERMOSA BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
05
Purpose
Capital Improvement Program Assesment
Project
20210503MDM_SOUTH_BAY_CITIES_MAIN_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
30 0068
Downstream MH
30 0069
Dir. of Survey
Upstream
Length Surveyed
205.8 ft.
Total Length
205.8 ft.
Structural Index
3
Structural Quick
5143
Structural Rating
33
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
37
Pipe schematic from manhole 30 0068 to 30 0069
MH: 30 0068MH: 30 0069upstream0 ft. AMH - Downstream Manhole, Survey Ends - 3:25AM0.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE0.7 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE0.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.7 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active13.9 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR62.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE101.2 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE ROCKS111 ft. RPP - Repair Patch, from 12 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH114.4 ft. MMC - Material Change, Reinforced concrete pipe114.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG120 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG 1 SECTION RCP139.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H141.3 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - H153.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H161.6 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE164 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT169.8 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - HAILINE190.4 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SLIGHT192.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE193.5 ft. MMC - Material Change, Vitrified clay pipe193.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG203.8 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG205.8 ft. AMH - Upstream Manhole, Survey Begins - 2:45AM205.8 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active205.8 ft. MWL - Water Level, 10 %of cross sectional area205.8 ft. MWM - Water Mark, 20 %of cross sectional area

Observation photos (9)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Material Change, Vitrified clay pipe

    12.3 ft. - Material Change, Vitrified clay pipe

  • Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

    41.8 ft. - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SLIGHT

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG 1 SECTION RCP

    85.8 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG 1 SECTION RCP

  • Material Change, Reinforced concrete pipe

    91.4 ft. - Material Change, Reinforced concrete pipe

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    91.4 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Repair Patch, from 12 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

    94.8 ft. - Repair Patch, from 12 to 05 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    143.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    191.9 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

Observations (27)

DistanceCodeObservation
205.1SSSBLISTERING PEELING CONCRETE
94.8RPPCONCRETE PATCH
205.8AMH3:25AM
44.2DSZSLUDGE
12.3MMC
191.9SRVCIRCUM REBAR
36FCHAILINE
41.8FCSLIGHT
0AMH2:45AM
205.1DSZSLUDGE
2SAMSEVERE AGG
0MGOConn. @ Mh, 9 O' Clock. Active
0MWL
205.1SAMSEVERE AGG
143.3SSSBLISTERING PEELING CONCRETE
85.8SAMSEVERE AGG 1 SECTION RCP
91.4MMC
66.4FLH
205.1MGOConn. @ Mh, 9 O' Clock. Active
52.6FCH
91.4SAMSEVERE AGG
15.4FCSLIGHT
12.9DSZSLUDGE
104.6DSZSLUDGE ROCKS
64.5FLH
0MWM
12.3SAMSEVERE AGG

Properties (6)

custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2021-05-03T02:40:42-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA