Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2021, 10:28 AM
  • 30 0070_30 0069_532021_033101.mp4

Date
05/03/2021
W/O
0886345
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00878
PipeID
P17773
Time
3:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1795
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
HERMOSA BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
05
Purpose
Capital Improvement Program Assesment
Project
20210503MDM_SOUTH_BAY_CITIES_MAIN_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
30 0069
Downstream MH
30 0070
Dir. of Survey
Upstream
Length Surveyed
260.9 ft.
Total Length
260.9 ft.
Structural Index
4
Structural Quick
5342
Structural Rating
25
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
31
Pipe schematic from manhole 30 0069 to 30 0070
MH: 30 0069MH: 30 0070upstream0 ft. AMH - Upstream Manhole, Survey Ends - 4:05AM0.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE0.7 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG0.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE17.4 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE17.4 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG17.4 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE44.2 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR102.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active184.3 ft. SRC - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR195.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - SLUDGE195.2 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE242.5 ft. SRC - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR247.5 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - SLUDGE258.9 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG258.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE260.9 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active260.9 ft. MWM - Water Mark, 20 %of cross sectional area260.9 ft. MWL - Water Level, 10 %of cross sectional area260.9 ft. AMH - Downstream Manhole, Survey Begins - 3:35AM

Observation photos (6)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    18.4 ft. - Surface Reinforcement Corroded, from 01 to 03 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    76.6 ft. - Surface Reinforcement Corroded, from 12 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    216.7 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    243.5 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

Observations (20)

DistanceCodeObservation
260.2SSSBLISTERING PEELING CONCRETE
243.5DSZSLUDGE
2SAMSEVERE AGG
0MGOConn. @ Mh, 9 O' Clock. Active
0MWM
158.3TFAActive
216.7SRCCIRCUM REBAR
243.5SAMSEVERE AGG
0MWL
13.4DSZSLUDGE
260.2SAMSEVERE AGG
243.5DSZSLUDGE
18.4SRCCIRCUM REBAR
65.7DSZSLUDGE
76.6SRCCIRCUM REBAR
65.7DSZSLUDGE
260.9AMH4:05AM
260.2DSZSLUDGE
2SSSBLISTERING PEELING CONCRETE
0AMH3:35AM

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED
custom_field_two
2
customer
LACSD
datetime
2021-05-03T03:28:17-07:00
documentation
MARTIN,OLIVER 111,CASTILLO,RUVALCABA
is_lateral_inspection
false