Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 7, 2021, 08:27 AM
  • 15 0058_15 0057_04072021_015247.mp4

Date
04/07/2021
W/O
887826
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00622
PipeID
P11951
Time
1:27 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8812
Sewer Name
15 PUENTE TRUNK
City
CITY OF INDUSTRY
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
CA_WO_887826
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0058
Downstream MH
15 0057
Dir. of Survey
Downstream
Length Surveyed
113.1 ft.
Total Length
113.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0058 to 15 0057
MH: 15 0058MH: 15 0057downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 00588 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"31.1 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"57.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"84.3 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"91.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES94.8 ft. CS - Crack Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES107.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"112.8 ft. OBM - Obstacles Pipe Material, 5 %of cross sectional area, at 06 o'clock113.1 ft. MSA - Survey Abandoned - DUE TO PIPE MATERIAL IN LINE

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    91.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

    94.8 ft. - Crack Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Obstacles Pipe Material, 5 %of cross sectional area, at 06 o'clock

    112.8 ft. - Obstacles Pipe Material, 5 %of cross sectional area, at 06 o'clock

  • Survey Abandoned - DUE TO PIPE MATERIAL IN LINE

    113.1 ft. - Survey Abandoned - DUE TO PIPE MATERIAL IN LINE

Observations (12)

DistanceCodeObservation
113.1MSADUE TO PIPE MATERIAL IN LINE
0MWL
0MWM
94.8CS
57.9TF
112.8OBM
107.9TFC
8TFC
0AMH15 0058
91.6CM
31.1TFC
84.3TFC

Properties (6)

custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-04-07T01:27:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false